HOME  /  PRODUCTS  /  Process Indicator  /  Digital Panel Meter  /  4 Digital Process meter
4 Digital Process meter
CM2-PR
4 Digital Process meter

Description

CM2-PR Process Meter has been designed in simple operation and 4 digital 20mm LED display with economic cost. They are can be programmed by buttons that are hidden in front panel. They are also available to option 2 relay output and an analog output or RS485(Modbus RTU Mode) communication.

 

Features

 Measuring 0(1)~5V/0~10V, 0~10mA/0(4)~20mA

 Optional DC24V excitation power for 2 wire sensors

 The operation buttons are built-in to prevent users from arbitrary operation or incorrect setting, which may cause abnormal operation of the equipment

 The display value can be adjusted slightly with the "field measurement signal"

 The output can option relays and analog output or RS485 (Modbus RTU mode)

 Relay function in addition to start delay, active delay, delay off and active hold

 Analog output voltage signal range can be switched (0~10V/0~5V/1 ~5V) or current signal range can be switched (0~10mA/0~20mA/4~20mA)

 The analog output signal is free to set the corresponding display range (Span-50%) and can be fine-tuned on-site

 On board terminal design, no quality issue; installation depth is only 72mm

 

Applications

 2 wire sensing transducers as like as pressure, level and so on…

 Process alarm or communication for data collection

Summary of specifications
  • Summary of Specifications
  • Selection Information
  • Related Products

Specification & Function

Input

CM2_PR_input_EN

  • Accuracy: ±0.1% of FS±1 count
  • Sampling rate: 15 times/sec
  • Response time: ≤ 100 mS(when avg = “1”)

Display & Function

  • LED: 4 digits,0.8”(20.0mm) high-brightness LED
  • Display range: -1999~+9999
  • Scaling function:
    • lOsc: Low Scale:-1999~+9999
    • hIsc: High Scale:-1999~+9999
  • Decimal point: dp: 0 / 0.0 / 0.00 / 0.000
  • Over range Indication: ovfl: when input is over 110% of input range
  • Under range indication: -ovfl: when input is under lOsc value
  • Max / Mini recording: Maximum and Minimum value storage during running
  • Low cut: -1999~+9999 counts

Datasheet

Version: 1.0 / Update: 2022.02.16

 

Manual-SV

Version: 1.0 / Update: 2020.07.16

CM2_PR_Selection_EN