Description
CM1-PR Indicator has been designed in simple function and 4 digital 20.0mm LED displays with economic cost. They are can be programmed by tact switches that are hidden in backside of front bezel. They are also available option of 2 Relay outputs, 1 Analogue output or 1 RS485(Modbus RTU Mode) interface with versatile functions such as control, alarm, re-transmission or communication for a wide range of industrial applications.
Features
■ Measuring 0(1)~5V/0~10V, 0~10mA/0(4)~20mA ( or 2 wire sensor with 24Vdc excitation supply )
■ Optional DC24V excitation power for 2 wire sensors
■ The operation buttons are built-in to prevent users from arbitrary operation or incorrect setting, which may cause abnormal operation of the equipment
■ The display value can be adjusted slightly with the "field measurement signal"
■ The output can option relays or analog output or RS485 (Modbus RTU mode)
■ Relay function in addition to start delay, active delay, delay off and active hold
■ Analog output voltage signal range can be switched (0~10V/0~5V/1 ~5V) or current signal range can be switched (0~10mA/0~20mA/4~20mA)
■ The analog output signal is free to set the corresponding display range (Span-50%) and can be fine-tuned on-site
■ On board terminal design, no quality issue; installation depth is only 72mm
Applications
■ 2 wire sensing transducers as like as pressure, level and so on…
■ Process alarm or communication for data collection
- Summary of Specifications
- Selection Information
- Related Products
Specification & Function
Input:
- Calibration: Digital calibration
- A/D converter: 14 bits
- Accuracy: ≤ ± 0 .1% of FS ±1 count
- Sampling rate: 15 times / sec
- Response time: ≤ 100 mS (when avg = “1”)
Display & Function
- LED: 4 digits, 0.8”(20.0mm) red high-brightness LED
- Display range: -1999~+9999
- Scaling function:
- [ lOsc]: -1999~+9999
- [ hIsc]: -1999~+9999
- Decimal point: Programmable from 0 / 0.0/ 0.00/ 0.000
- Over range indication: [ ovfl]: when input is over 110% of input range Hi
- Under range indication: [-ovfl]: when input is under[ losc]setting value
- Max /Mini recording: Maximum and Minimum value storage during running
- Low cut: [lOcut] -1999~+9999 counts